LNG immersed pump skid
PRODUCTS CENTER
south sudan republic LNG station complete equipment (test)
+86-15601559666
Product Description
LNG station complete equipment
Summary
LNG station can be divided into 2 types: skid-mounted LNG station and stationary LNG station. Skid-mounted LNG station is to integrate storage tank, pump skid, PLC control system and LNG dispenser in one skid, which is convenient to transport the full station. Stationary LNG station is to install storage tank, pump skid, PLC control system and LNG dispenser in the station.
Main equipment composition: cryogenic storage tank, LNG cryogenic immersed pump, LNG unloading skid, instrument wind system, PLC control system etc. Main function: LNG unloading, pressure regulating, LNG filling, metering etc. Main
advantages: modular design, high integration level, convenient and efficient installation.
Main functions
Unloading: unload LNG from tank car to storage tank through self-pressurization and pump.
Refueling: refuel LNG to vehicle cylinder through cryogenic pump and LNG dispenser.
Pressure boosting: filling partial LNG into LNG storage tank after vaporized to meet tank setting value
Saturation regulating: pumping partial LNG to vaporizer from storage tank by LNG cryogenic pump, and return to the bottom of storage tank after vaporization, which increases the temperature of LNG storage tank thereby increase the storage tank pressure.
1.1 Skid-mounted LNG station
Summary
Skid-mounted LNG station is the complete LNG refueling system which assembled, tested and debugged in factory. This kind of system integrates LNG storage tank, LNG immersed pump, PLC control system and LNG dispenser in the skid, which is convenient to transport the full station. It can finish unloading, pressure regulating and refueling independently. It can be divided into 2 types: skid-mounted LNG station and container LNG station.
Key Parameter
|
Model |
YN-JYQ-Q30A |
YN-JYQ-Q60A |
|
Working medium |
Liquefied Natural Gas(LNG) |
|
|
Total volume of storagetank |
30m3 |
60m3 |
|
Heatinsulation of storagetank |
High vacuum twine / High vacuum pearlife padding |
|
|
NO.of pumps |
1 unit |
2 units |
|
Max.discharge of pump |
340L/ min |
680L/ min |
|
Operating pressure |
1.6 Mpa |
|
|
Measurin gaccuracy |
±1.0% |
|
|
Pipeline design temperature |
-196℃ |
|
|
Total power |
15KW |
30KW |
|
Noise |
≤55dB |
|
|
Explosive-proof grade |
Exd ⅡBT4 |
|
|
Control mode |
PLC full automatic control |
|
1.2 Stationary LNG station
Summar
Stationary LNG station is the LNG refueling system that is composed of 4 subsystems: LNG storage tank, LNG pump skid, LNG dispenser and PLC control cabinet. Each module finishes assembling, testing and debugging in factory. The station can be put into trial operation after each module connected, installed and debugged simply at site.
Key Parameter
|
Model |
YN-JYQ-AD1A |
YN-JYQ-AD2A |
|
Working medium |
Liquefied Natural Gas( LNG) |
|
|
NO.of pumps |
1unit |
2units |
|
Max.discharge of pump |
340L/ min |
680L/ min |
|
Operating pressure |
1.6 Mpa |
|
|
Pipeline design temperature |
-196℃ |
|
|
Total power |
15KW |
30kW |
|
Noise |
≤55dB |
|
|
Explosive-proof grade |
Exd ⅡBT4 |
|
|
Vaporizer |
300 + 150Nm3 |
|
|
Dimension |
3500*2400*2400( mm ) |
|
|
Control mode |
PLC full automatic control |
|
|
Model |
YN-JYQ-AD1A |
YN-JYQ-AD2A |
1.2.1 LNG Skid-mounted Pump
Summary
LNG pump skid is to integrate LNG cryogenic immersed pump, vacuum pump pool, vaporizer, vacuum pipeline and valves in the skid, which has functions of unloading, pressure regulating and refueling. Equip with safety precautions such as combustible gas detection, leakage alarm, emergency cut-off etc. Multiple unload mode: pump unload, self-pressurization unload, combined unload etc. Multiple functions: storage tank pressure boost, thermoregulation, instant refuel during unload, dual pump crossed standby application.Pump pool uses high vacuum twine heat insulation, inflow & outflow pipeline use PIR cold insulation mode, which keeps the cold loss to a minimum. Reuse the BOG in storage tank by our particular unloading equal pressure mode.
Advantages
High integration, easy installation, safe and reliable, advanced technological process, cold loss control.
1.2.2 LNG dispenser
Summary
Accuracy of measuring reaches ± 1%. Function of pipeline pressure limiting protection, which realizes overpressure protection through safety valve and pressure sensor. Advanced cold insulation technology - insulation treatment for all inner medium circulation pipelines (including mass flow meter), reduce BOG effectively. Repeated operation is unnecessary as liquid filling interval time is short, which will reduce gas filling waiting time. The operation mode single pumpdual dispensers and “ dual pumps four dispensers come true through interconnected control.
Advantages
High accuracy of measuring、High security、Reasonable technological process Good thermal insulation properties, low loss.
Main functions
● Refuel by non-quantitative and preset volume
● Measuring by mass and volume
● Explosive-proof design: intrinsic safety and isolating safety
● Breakaway coupling
● Save data automatically after power cut, display data lingeringly
● Display unit price, volume and sum with high light backlit LCD
● IC card management, auto settlement and favorable unit price
● Bill printer
● Pressure temperature compensation function
● Stop automatically after refueling completed
● Data transmission communication interface
Key Parameter
|
LNG dispen serseries technical parameters |
|
|
Applicable medium |
Liquefied natural gas |
|
Range offlow |
3 ~80kg/min |
|
Accuracy of measuring |
±1.0% |
|
Working Pressure |
1.6 MPa |
|
Ambient temperature |
-40℃-+55℃ |
|
Pipeline temperature |
-196℃-+55℃ |
|
Ambient Humidity |
≤95% |
|
Ambient Atmosph ere |
86 ~ 110Kpa |
|
Unit of measurement |
Kg、 L、 Nm3 |
|
Minimum scale reading |
0.01 |
|
Single counter Range |
0 ~9999.99 |
|
Totalize range |
99999999.99 |
|
Refueling Hose |
1 inch stainless steel flexible hose(4m/6m) |
|
Gas phase recovery hose |
1/2 inch stainless steel flexible hose(4m/6m) |
|
Filling nozzle |
1 inch special use for LNG dispenser |
|
Gas phase pipe joint |
1/2 inch quick coupling |
|
Power supply |
220V ±15% 50Hz ±1 HZ |
|
Explosive-proof grade |
Complete Machineanti-explosion Exdefbmb ⅡAT4Gb |
|
Rated power |
200W |